Professional Manufacturer of One Stop Solutions Provider for all kind of lithium battery 10 years more .

English

What are the preparation methods of UPS lead-acid battery electrolyte?

by:Vglory      2021-03-20
UPS lead-acid battery electrolyte preparation method (1) The container for preparing battery electrolyte should be acid-resistant glass ceramic, hard rubber or lead container (2) for full protection. When preparing electrolyte, operators must wear protective glasses, acid-proof gloves, rubber aprons and high-waist rubber boots to prevent burns. Once the sulfuric acid splashes on the clothes, they should be soaked with 10% soda solution (sodium carbonate) immediately, and then rinsed with water. (3) Preparation method. According to the required electrolyte, calculate the amount of distilled water and sulfuric acid according to the mixing ratio. (4) Measure out the calculated distilled water with a graduated cylinder and pour it into the acid-resistant capacity for preparing the electrolyte. (5) Measure out the required amount of sulfuric acid, slowly add it to the water, and continuously stir with a glass rod or a plastic rod to mix the two evenly and quickly dissipate heat. Disclaimer: Some pictures and content of articles published on this site are from the Internet. If there is any infringement, please contact to delete. Previous article: What are the technical requirements for installing UPS power batteries?